Categories: Featured Articles » Electrician at home
Number of views: 53449
Comments on the article: 10

Grounding device for a country house

 

Grounding device for a country houseDevice need re-grounding at the entrance to the country house is dictated by the current rules of the PUE. In accordance with paragraph 1.7.61 of these rules at the input to any electrical installation grounding systems TN installation of a grounding device with a current spreading resistance of 30 ohms for a three-phase network and 60 ohms for a single-phase network is recommended. These recommendations can only be neglected if available and used. natural grounding (metal structures partially located in the ground and meeting the requirements of the PUE for resistance).

Since it is far from always possible to choose a suitable natural grounding conductor, the device of a separate grounding device (charger) at the entrance to the newly built country house becomes the most rational technical solution. Moreover, it does not require special material costs.


Grounding device includes a grounding conductor, as well as a grounding conductor located directly in the ground. Ground conductor - a conductive conductor connecting the PE bus (main grounding bus, or GZSh) to the ground electrode. The cross section of this conductor is normalized by table 1.7.5 of the EIC and depends on the cross section of the phase conductors.

So, if the phase lead-in conductor has a cross section of 16 square meters. mm or less, the ground conductor must have a cross section equal to or greater than the cross section of the phase conductor. With a larger cross section of the phase input conductor, the ground conductor may have a cross section equal to half the cross section of the phase conductor.

Of course, we are talking about those cases when the materials of the phase and ground conductors coincide. If this is not so, then it is necessary to take into account the difference in the resistivity of the conductive materials. It is possible to use grounding conductors having a cross section less than recommended by table 1.7.5 (see PUE), but only if a calculation is made confirming that mains short circuit current will be of sufficient size to trigger protection.

For the installation of grounding conductors, preference is usually given to multi-wire copper wires in single-yellow polyvinyl chloride insulation (yellow-green) (PV-3) Grounding conductor on the earthing side crimped with cable lug and sits on a steel bolt, and from the side of the GZSH it is fastened either under a clamp with preliminary tinning, or again with a bolt and a tip - depending on the design of the tire itself.

The earthing switch is structurally composed of horizontal conductorslaid in the ground and directly vertical grounding electrodes. The material of both those and others may be different.

In accordance with the technical circular No. 11/2006 from the Roselectromontazh Association, which clarifies and supplements the PUE standards, bringing them into line with international standards, it is allowed to make earthing switches from black steel, steel with various types of coating, from tinned or galvanized copper, or from copper without any coating.

The cross-sectional shape of the grounding electrodes and conductors laid in the ground may also be different. It can be a corner, strip, pipe, bar. For each of these sections, the minimum size and minimum dimensions in any direction are normalized. So, for example, the use of a black steel strip thinner than 5 mm is excluded, even if its cross-sectional area is normal and is at least 150 square meters. mm These limitations are related to the corrosion resistance of the ground electrode material.

The grounding conductors are connected either by weldingor bolted. Other connection methods are not allowed.

The most popular technical solution for the earthing device is the vertical installation in the ground of three steel bars with a diameter of 18 mm and a length of 2.5-3 meters, connected by a steel strip of 40 * 5 mm. The bars are located at the vertices of an imaginary equilateral triangle. This whole structure is located at a depth of 0.5 meters underground.

To make the conclusion necessary for connecting the grounding conductor, you can use the same strip welded to the grounding and displayed on the wall of the house in any convenient place.

Upon completion of work related to the device for re-grounding at the entrance to the house, it is necessary to invite specialists from a registered electrical laboratory to take measurements and issue a protocol confirming the fact that the electrical resistance of the ground electrode is within normal limits.

Alexander Molokov

See also at e.imadeself.com:

  • Power supply of a country house
  • Installation practice and modular grounding features
  • Grounding wire - cross-section, marking, color, connection, requirements for charging ...
  • Ground home wiring, ground loop in a private house
  • Electric installation work when connected to the electricity supply of a country house

  •  
     
    Comments:

    # 1 wrote: | [quote]

     
     

    It is not entirely clear - why re-ground the power supply of a country house? The fact that it is recommended is not sufficient for its unconditional implementation. You can also understand the grounding, for example, electric stoves or electric boilers, if they are not zeroed. But ground the power grid? And what are the consequences in emergency conditions when the phase gets to the neutral wire?

    And one more thing: it’s much more important for safety to install an RCD and choose circuit breakers with electromagnetic releases that reliably operate during short-circuit at the most remote point. The latter is not always true, and country houses and summer cottages are on fire.

     
    Comments:

    # 2 wrote: | [quote]

     
     

    Anatolia: Well, there are no “less” and “more” important safety rules. Here it is specifically said about grounding, although RCDs and so on are no less important. And grounding should be common and included in the potential equalization system.

    You do not need to ground the network - you need to re-ground the neutral conductor at the input. The emergency mode associated with the phase getting to zero leads to the operation of overcurrent protection and nothing more.

     
    Comments:

    # 3 wrote: Ibrahim | [quote]

     
     

    they told me to do grounding and I did

     
    Comments:

    # 4 wrote: Nikolay | [quote]

     
     

    Everything is written very well and clearly. I like it. Useful.

     
    Comments:

    # 5 wrote: | [quote]

     
     

    when the neutral conductor breaks in the three-phase network, the appearance of increased voltage in sockets is possible. and therefore it is forbidden to "nullify" electrical appliances, life is more important)))

     
    Comments:

    # 6 wrote: Alik | [quote]

     
     

    For general development, so to speak))) I do not recommend making a contour of ferrous metal, galvanizing is best suited for this purpose. Welding? Oh no! Only a bolted connection and then the circuit will serve for many years. Otherwise, corrosion will do its job and in five years all this piling up will be simply useless, wasted money in vain, although ... if for a purely formal case - I did the job, I earned the loot, and then the grass does not grow there)))

     
    Comments:

    # 7 wrote: | [quote]

     
     

    Thanks. I'll know!

     
    Comments:

    # 8 wrote: | [quote]

     
     

    Purely practical! The installers mixed up and applied the phase to the "0" input shield (220/380 network), of course, in the part of the outlets, the increased total burned so much that the owner took up his head, the protection did not work because the grounding was performed incorrectly and did not meet the requirements of the PUE, the meter simply showed a load of 6 kW (Mercury-233) with the outgoing circuit breakers of the input shield turned off, which means a mismatch in the loop resistance.

     
    Comments:

    # 9 wrote: | [quote]

     
     

    Thanks for the newsletter.
    A sample protocol is required.
    Thank you in advance.

     
    Comments:

    # 10 wrote: | [quote]

     
     

    The equipment will not save grounding from supplying the phase to the working zero of the sockets, as well as when applying the phase to the grounding device (if the electrical installation is up to 1000V). However, when I burn off zero, I think it will align several potentials.

    I don’t understand why this triangle is offered everywhere? Contour grounding devices have a mutual shielding of the electrodes (loss of efficiency). Beat the line.

    And if you like, after all, a contour grounding device, it is necessary to carry the electrodes far (at least to place along the perimeter of the building, though the foundation will be somewhat disturbing here), and this is already very ruinous on the strip :-)